Below are typical and proven configurations for a standard CCI installation.
4.1 Flow: PV → Consumption / Accumulation
| Device | Order | Justification |
| Heating pump | 1 | Direct consumption, high contribution |
| EV charger | 2 | Flexible consumption |
| BESS (charging) | 3 | Storage only after consumption |
| GRID (export) | - | Only residual energy |
4.2 Flow: Production / BESS → GRID (reserved power)
Equipment | Attenuation order | Justification |
| BESS (discharge) | 1 | Fastest regulation |
PV | 2 | Restriction only after BESS |
| Scenario: drop in consumption → first, BESS discharge is reduced, then PV power. | ||
4.3 Flow: GRID → Consumption / Accumulation (reserved power input, protection)
Equipment | Order | Justification |
EV charger | 1 | Most flexible consumption |
| Heating pump | 2 | Can be limited in the short term |
| BESS (charging) | 3 | Can be limited during overload |
Other technologies 4-6 According to criticality | ||
4.4 Summary of recommended priorities
Energy flow | Priority 1 | Priority 2 | Priority 3 |
| PV → consumption | Heating pump | EV charger | |
| BESS Export to GRID | BESS | ||
PV | |||
| GRID → consumption | EV charger | Heating pump | BESS |